Individual & Overall Screened & Armored Thermocouple Cable

Application

These cables are suitable for underground use in industries where hydrocarbon may be present and where chemical and mechanical protections are required.

Standards

  • IEC 60584-3
  • NF C 42-324

Cable Construction

images/Individual & Overall Screened & Armored Thermocouple Cable.jpg

Construction

Conductor Metal according to thermocouple type
Insulation PVC
Individual screen Aluminum/polyester tape with tinned copper drain wire
Individual sheath PVC
Overall screen Aluminum/polyester tape with tinned copper drain wire
Sheath Special PVC. Color depends on thermocouple type

Properties

Flame retardance NFC 32070 C2, IEC 60332-1-2
Operating voltage 250V
Operating temperature -20~60°C
Max. conductor temperature in service 70°C
Chemical resistance Aliphatic and aromatic hydrocarbon resistance
Conductor Size No. of Pairs Min. O.D. Max. O.D. Approx. Weight
mm2   mm mm kg/km
0.5 solid 3 11.1 12.8 180
0.5 solid 7 15.4 17.7 335
0.5 solid 12 19.8 22.8 545
0.5 solid 19 24.6 28.1 825
0.5 solid 27 28.9 33.2 1135